COMPLY AS FOLLOWS:
- Ensure that the fire alarm system is inspected twice a year by a certified company. Available documentation revealed one fire alarm inspection in 2017, dated 6/29/17.
- Ensure that all smoke detectors are tested for sensitivity every two years. There was no available documentation of smoke detector sensitivity testing.
- Mechanically protect the circuit breaker supplying power to the fire alarm system.
- Ensure that the sprinkler system is inspected annually by a certified company and quarterly by qualified personnel.
- Provide a 5 year sprinkler system inspection consisting of an internal pipe inspection and calibration/replacement of pressure gauges.
- Provide service to a sprinkler head in the corridor outside Cell 8. There was an excess buildup of dirt on the sprinkler head.
- Ensure that the kitchen hood and duct extinguishment system is inspected twice a year by a certified company. Available documentation revealed one inspection of the system in 2017.
- Provide monthly visual inspections of the components of the kitchen hood and duct extinguishment system.
- Provide monthly visual inspections for all fire extinguishers.
- Provide service to the fire extinguisher in the Communications Center. There was no inspection tag on the extinguisher.
- Provide testing for all battery backup emergency lighting units consisting of monthly testing for 30 seconds and annual testing for 90 minutes.
- Provide weekly inspections for all components of the generator set.
- Provide monthly tests under load for the generator set for a minimum of 30 minutes, using one of the following methods:
A: Loading that maintains the minimum exhaust temperatures as recommended by the manufacturer.
B: Under operating temperature conditions and at not less than 30 percent of the generator set nameplate
KW rating.
- Provide a cover for the open space in Electrical Panel EP.
Provide a written plan of correction, including completion date, to Curtis Seddon at: seddon@dps.state.ia.us. The plan of correction shall be returned within 15 calendar days from receipt of report.